NAME
riello_ser - Driver for Riello UPS Protocol UPS equipment via serial port connections
SYNOPSIS
riello_ser -h
riello_ser -a UPS_NAME [OPTIONS]
Note
This man page only documents the hardware-specific features of the riello_ser driver. For information
about the core driver, see nutupsdrv(8).
SUPPORTED HARDWARE
riello_ser supports all recent Riello UPS, Aros UPS models which use the Riello UPS GPSER and SENTR
protocols.
Older Riello UPS products are not supported.
EXTRA ARGUMENTS
You may need to tweak some settings, depending on the make and model of your UPS (see ups.conf(5)):
localcalculation
When enabled, driver will calculate values of battery.runtime and battery.charge "locally" in the
driver. This is for some Riello models which provide incorrect values in hardware readings, or none
at all. This "local calculation" is done according to nominal battery capacity, nominal battery
voltage, actual battery charge, maximum and actual UPS load.
You may want to also configure default.battery.voltage.low and default.battery.voltage.high in case
the built-in default range (from 10.7V to 12.9V) does not match your hardware, or give a shot to
default.battery.voltage.nominal (e.g. 24) if your device does not serve that either.
Note
Lead (PbAc) battery charge graph is not linear, so guesstimated charge value may not be perfectly
accurate. However it should be good enough to determine battery actual status and roughly
estimate the time it can still power the system.
Warning
This keyword may be deprecated in future releases of the driver, in favor of runtimecal and other
settings which it requires (as seen in nutdrv_qx(8), blazer_ser(8) and blazer_usb(8) drivers).
AUTHOR
Massimo Zampieri
SEE ALSO
Related drivers
riello_usb(8)
The core driver
nutupsdrv(8)