Provided by: nut-server_2.8.3-2_amd64 bug

NAME

       nutdrv_siemens_sitop - Driver for the Siemens SITOP UPS500 series UPS

SYNOPSIS

       nutdrv_siemens_sitop -h

       nutdrv_siemens_sitop -a UPS_NAME [OPTIONS]

           Note

           This man page only documents the hardware-specific features of the nutdrv_siemens_sitop driver. For
           information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE

       nutdrv_siemens_sitop supports Siemens UPS models from the SITOP UPS500 series. Some models have a serial
       port, others have a USB port. The models with USB port actually contain a serial-over-USB chip, so as far
       as this driver is concerned, all models are serial models. This driver should work with all models in the
       SITOP UPS500 series, as long as your kernel has support for the serial port device (see section USB
       driver below).

           Note

           This driver has only been tested with the SITOP UPS500S-2.5 with USB port (Siemens product number
           6EP1933-2EC41).

DEVICE SETTINGS

       The UPS is configured via DIP-switches. For correct functioning in combination with NUT, set the
       DIP-switches to the following:

       switch 1-4
           Choose whatever suits your situation. Any combination will work with NUT.

       switch 5 (⇒ / t)
           Set to OFF (t). This ensures that the UPS will not cut power unless NUT tells it to do so (or unless
           the batteries are exhausted).

       switch 6-10 (delay)
           Set to OFF (minimum delay). Setting a higher delay will actually also work, but any command from NUT
           will be delayed as well before being executed by the UPS. With the minimum setting, it will already
           take 5 seconds before a command from NUT is executed.

       switch 11 (INTERR.)
           Set to ON (interrupt the output after the timer expires). This ensures that the UPS briefly
           interrupts the output power in response to the shutdown.return command. See the section Instant
           Commands below.

       switch 12 (ON/OFF)
           set to ON (enable the UPS functionality). Without this, the UPS will never supply power from its
           batteries.

USB DRIVER

       The USB-versions of the UPS contain an FTDI USB-to-serial converter chip. It is programmed with a
       non-standard product ID (for example 0403:e0e3), but can still be used with the normal ftdi_sio driver.

           Note

           The following hints may be specific to GNU/Linux.

       Use lsusb to figure out which product ID is used in your model, and replace all occurrences of e0e3 in
       the following examples with the actual Product ID.

           modprobe ftdi_sio
           echo 0403 e0e3 > /sys/bus/usb-serial/drivers/ftdi_sio/new_id

       If your system uses udev, this can be automated via an udev rule:

           ACTION=="add", ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3", \
             RUN+="/sbin/modprobe ftdi_sio", \
             RUN+="/bin/sh -c 'echo 0403 e0e3 > /sys/bus/usb-serial/drivers/ftdi_sio/new_id'"

       You can use the following udev rule to obtain a predictable device name, for example /dev/ttyUPS:

           SUBSYSTEM=="tty" ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3" SYMLINK+="ttyUPS"

POLLING

       The UPS does not have a special get status command. Instead, it continuously sends out status update
       messages (tens of messages per second). Every pollinterval, these messages are read from the serial port
       buffer.

       In order to react quickly on status changes from the UPS, and to prevent the serial buffer from
       overflowing, pollinterval should be set to a relatively low value. The recommended value is 1 (second).

EXTRA ARGUMENTS

       This driver supports the following optional settings:

       max_polls_without_data=num
           The serial port is polled periodically for new data (see Polling). If there is no valid new data
           after num polls, it is assumed that communication with the UPS is lost.

           The default value is 2. Lower values may cause spurious Data stale messages, especially at startup.

INSTANT COMMANDS

       shutdown.return
           The behavior of this command depends on the line state:

           •   on line: after 5 seconds (or longer, if DIP switches 6-10 are not OFF), the UPS will shut off its
               output. After another 5 seconds, the output is activated again.

           •   on battery: after 5 seconds (or longer, if DIP switches 6-10 are not OFF), the UPS will shut off
               its output. The output will stay off, until the line voltage has returned.

       shutdown.stayoff
           The behavior of this command depends on the line state:

           •   on line: after 5 seconds (or longer, if DIP switches 6-10 are not OFF), the UPS will shut off its
               output. The output stays off, until the line voltage has been removed for at least 1 second, and
               has been re-applied.

           •   on battery: this command behaves the same as shutdown.return.

INSTALLATION

       Make sure that your operating system has created a serial device for the UPS. See the section USB driver
       for more information.

       Next, make sure that NUT has access rights to this device file. For example, by creating an udev rule
       that grants permission to the NUT user, or by adding the NUT user to a user group that can access serial
       devices (e.g. the dialout group on Debian-based systems).

DIAGNOSTICS

       You can verify the correct functioning of the hardware, by monitoring the serial port with a terminal
       program, for example picocom:

           :; picocom -b 9600 -d 8 -p n /dev/ttyUPS

       NUT must not be running when you do this. You should now see a continuous stream of 5-character texts
       coming in, for example:

           BUFRD
           BA>85
           DC_OK

       To exit picocom, use Ctrl-A Ctrl-X.

KNOWN ISSUES AND BUGS

       Untested models
           As mentioned under Supported hardware, this driver has not been tested with all models in the SITOP
           UPS500 series.

       Data stale messages
           The firmware in these UPSes is quite buggy. After sending data to the UPS, it sometimes stops sending
           status updates. This driver tries to prevent this (e.g. by sending commands twice, and by sending
           additional LF characters after each command).

           Once the UPS is in this state, communication can only be restored by rebooting the UPS, or by
           unplugging and reconnecting the USB cable.

           During normal operation, no commands are sent to the UPS at all (only at shutdown), so this issue is
           expected to have little impact on usability.

           It is not certain if the serial models are affected by this issue as well.

AUTHOR

       Matthijs H. ten Berge

SEE ALSO

   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: https://www.networkupstools.org/historic/v2.8.3/

Network UPS Tools 2.8.3                            07/08/2025                            NUTDRV_SIEMENS_SITOP(8)