Provided by: nut-client_2.8.1-4ubuntu1_amd64 bug

NAME

       upsmon.conf - Configuration for Network UPS Tools upsmon

DESCRIPTION

       This file’s primary job is to define the systems that upsmon(8) will monitor and to tell it how to shut
       down the system when necessary. It will contain passwords, so keep it secure. Ideally, only the upsmon
       process should be able to read it.

       Additionally, other optional configuration values can be set in this file.

CONFIGURATION DIRECTIVES

       DEADTIME seconds
           upsmon allows a UPS to go missing for this many seconds before declaring it "dead". The default is 15
           seconds.

           upsmon requires a UPS to provide status information every few seconds (see POLLFREQ and
           POLLFREQALERT) to keep things updated. If the status fetch fails, the UPS is marked stale. If it
           stays stale for more than DEADTIME seconds, the UPS is marked dead.

           A dead UPS that was last known to be on battery is assumed to have changed to a low battery
           condition. This may force a shutdown if it is providing a critical amount of power to your system.
           This seems disruptive, but the alternative is barreling ahead into oblivion and crashing when you run
           out of power.

           Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT. Otherwise, you’ll have "dead"
           UPSes simply because upsmon isn’t polling them quickly enough. Rule of thumb: take the larger of the
           two POLLFREQ values, and multiply by 3.

       FINALDELAY seconds
           When running in primary mode, upsmon waits this long after sending the NOTIFY_SHUTDOWN to warn the
           users. After the timer elapses, it then runs your SHUTDOWNCMD. By default this is set to 5 seconds.

           If you need to let your users do something in between those events, increase this number. Remember,
           at this point your UPS battery is almost depleted, so don’t make this too big.

           Alternatively, you can set this very low so you don’t wait around when it’s time to shut down. Some
           UPSes don’t give much warning for low battery and will require a value of 0 here for a safe shutdown.

               Note
               If FINALDELAY on the secondary is greater than HOSTSYNC on the primary, the primary will give up
               waiting for that secondary upsmon to disconnect.

       HOSTSYNC seconds
           upsmon will wait up to this many seconds in primary mode for the secondaries to disconnect during a
           shutdown situation. By default, this is 15 seconds.

           When a UPS goes critical (on battery + low battery, or "FSD": forced shutdown), the secondary systems
           are supposed to disconnect and shut down right away. The HOSTSYNC timer keeps the primary upsmon from
           sitting there forever if one of the secondaries gets stuck.

           This value is also used to keep secondary systems from getting stuck if the primary fails to respond
           in time. After a UPS becomes critical, the secondary will wait up to HOSTSYNC seconds for the primary
           to set the FSD flag. If that timer expires, the secondary upsmon will assume that the primary (or
           communications path to it) is broken and will shut down anyway.

           This keeps the secondaries from shutting down during a short-lived status change to "OB LB" and back
           that the secondaries see but the primary misses.

       MINSUPPLIES num
           Set the number of power supplies that must be receiving power to keep this system running. Normal
           computers have just one power supply, so the default value of 1 is acceptable.

           Large/expensive server type systems usually have more, and can run with a few missing. The HP
           NetServer LH4 can run with 2 out of 4, for example, so you’d set it to 2. The idea is to keep the box
           running as long as possible, right?

           Obviously you have to put the redundant supplies on different UPS circuits for this to make sense!
           See big-servers.txt in the docs subdirectory for more information and ideas on how to use this
           feature.

           Also see the section on "power values" in upsmon(8).

       MONITOR system powervalue username password type
           Each UPS that you need to be monitor should have a MONITOR line. Not all of these need supply power
           to the system that is running upsmon. You may monitor other systems if you want to be able to send
           notifications about status changes on them.

       You must have at least one MONITOR directive in upsmon.conf.

       system is a UPS identifier. It is in this form:

       <upsname>[@<hostname>[:<port>]]

       The default hostname is "localhost". Some examples:

       •   "su700@mybox" means a UPS called "su700" on a system called "mybox". This is the normal form.

       •   "fenton@bigbox:5678" is a UPS called "fenton" on a system called "bigbox" which runs upsd(8) on port
           "5678".

       powervalue is an integer representing the number of power supplies that the UPS feeds on this system.
       Most normal computers have one power supply, and the UPS feeds it, so this value will be 1. You need a
       very large or special system to have anything higher here.

       You can set the powervalue to 0 if you want to monitor a UPS that doesn’t actually supply power to this
       system. This is useful when you want to have upsmon do notifications about status changes on a UPS
       without shutting down when it goes critical.

       The username and password on this line must match an entry in the upsd server system’s upsd.users(5)
       file.

       If your username is "observer" and your password is "abcd", the MONITOR line might look like this (likely
       on a remote secondary system):

       MONITOR myups@bigserver 1 observer abcd secondary

       Meanwhile, the upsd.users on bigserver would look like this:

           [observer]
                   password = abcd
                   upsmon secondary

           [upswired]
                   password = blah
                   upsmon primary

       And the copy of upsmon on that bigserver would run with the primary configuration:

       MONITOR myups@bigserver 1 upswired blah primary

       The type refers to the relationship with upsd(8). It can be either "primary" or "secondary". See
       upsmon(8) for more information on the meaning of these modes. The mode you pick here also goes in the
       upsd.users file, as seen in the example above.

       NOCOMMWARNTIME seconds
           upsmon will trigger a NOTIFY_NOCOMM after this many seconds if it can’t reach any of the UPS entries
           in this configuration file. It keeps warning you until the situation is fixed. By default this is 300
           seconds.

       POLLFAIL_LOG_THROTTLE_MAX count
           upsmon normally reports polling failures for each device that are in place for each POLLFREQ loop
           (e.g. "Data stale" or "Driver not connected") to system log as configured. If your devices are
           expected to be AWOL for an extended timeframe, you can use this throttle to reduce the stress on
           syslog traffic and storage, by posting these messages only once in every several loop cycles, and
           when the error condition has changed or cleared.

       A negative value means standard behavior, and a zero value means to never repeat the message (log only on
       start and end/change of the failure state).

       NOTIFYCMD command
           upsmon calls this to send messages when things happen.

           This command is called with the full text of the message as one argument. The environment string
           NOTIFYTYPE will contain the type string of whatever caused this event to happen.

           If you need to use upssched(8), then you must make it your NOTIFYCMD by listing it here.

           Note that this is only called for NOTIFY events that have EXEC set with NOTIFYFLAG. See NOTIFYFLAG
           below for more details.

           Making this some sort of shell script might not be a bad idea. For more information and ideas, see
           docs/scheduling.txt

           Remember, this command also needs to be one element in the configuration file, so if your command has
           spaces, then wrap it in quotes.

           NOTIFYCMD "/path/to/script --foo --bar"

           This script is run in the background—that is, upsmon forks before it calls out to start it. This
           means that your NOTIFYCMD may have multiple instances running simultaneously if a lot of stuff
           happens all at once. Keep this in mind when designing complicated notifiers.

       NOTIFYMSG type message
           upsmon comes with a set of stock messages for various events. You can change them if you like.

               NOTIFYMSG ONLINE "UPS %s is getting line power"

               NOTIFYMSG ONBATT "Someone pulled the plug on %s"

           Note that %s is replaced with the identifier of the UPS in question.

           The message must be one element in the configuration file, so if it contains spaces, you must wrap it
           in quotes.

               NOTIFYMSG NOCOMM "Someone stole UPS %s"

           Possible values for type:

           ONLINE
               UPS is back online

           ONBATT
               UPS is on battery

           LOWBATT
               UPS is on battery and has a low battery (is critical)

           FSD
               UPS is being shutdown by the primary (FSD = "Forced Shutdown")

           COMMOK
               Communications established with the UPS

           COMMBAD
               Communications lost to the UPS

           SHUTDOWN
               The system is being shutdown

           REPLBATT
               The UPS battery is bad and needs to be replaced

           NOCOMM
               A UPS is unavailable (can’t be contacted for monitoring)

           NOPARENT
               upsmon parent process died - shutdown impossible

           CAL
               UPS calibration in progress

           OFF
               UPS administratively OFF or asleep

           NOTOFF
               UPS no longer administratively OFF or asleep

           BYPASS
               UPS on bypass (powered, not protecting)

           NOTBYPASS
               UPS no longer on bypass

       NOTIFYFLAG type flag[+flag]...
           By default, upsmon sends walls global messages to all logged in users) via /bin/wall and writes to
           the syslog when things happen. Except for Windows where upsmon only writes to the syslog by default.
           You can change this.

           Examples:

               NOTIFYFLAG ONLINE SYSLOG
               NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC

           Possible values for the flags:

           SYSLOG
               Write the message to the syslog

           WALL
               Write the message to all users with /bin/wall

           EXEC
               Execute NOTIFYCMD (see above) with the message

           IGNORE
               Don’t do anything

               If you use IGNORE, don’t use any other flags on the same line.

       POLLFREQ seconds
           Normally upsmon polls the upsd(8) server every 5 seconds. If this is flooding your network with
           activity, you can make it higher. You can also make it lower to get faster updates in some cases.

           There are some catches. First, if you set the POLLFREQ too high, you may miss short-lived power
           events entirely. You also risk triggering the DEADTIME (see above) if you use a very large number.

           Second, there is a point of diminishing returns if you set it too low. While upsd normally has all of
           the data available to it instantly, most drivers only refresh the UPS status once every 2 seconds.
           Polling any more than that usually doesn’t get you the information any faster.

       POLLFREQALERT seconds
           This is the interval that upsmon waits between polls if any of its UPSes are on battery. You can use
           this along with POLLFREQ above to slow down polls during normal behavior, but get quicker updates
           when something bad happens.

           This should always be equal to or lower than the POLLFREQ value. By default it is also set 5 seconds.

           The warnings from the POLLFREQ entry about too-high and too-low values also apply here.

       POWERDOWNFLAG filename
           upsmon creates this file when running in primary mode when the UPS needs to be powered off. You
           should check for this file in your shutdown scripts and call upsdrvctl shutdown if it exists.

           This is done to forcibly reset the secondary systems, so they don’t get stuck at the "halted" stage
           even if the power returns during the shutdown process. This usually does not work well on
           contact-closure UPSes that use the genericups driver.

           See the config-notes.txt file in the docs subdirectory for more information. Refer to the section:

           "Configuring automatic shutdowns for low battery events", or refer to the online version.

       OFFDURATION seconds
           NUT supports an "administrative OFF" for power devices which can be managed to turn off their
           application workload, while the UPS or ePDU remains accessible for monitoring and management. This
           toggle allows to delay propagation of such state into a known loss of a feed (possibly triggering FSD
           on upsmon clients which MONITOR the device and are in fact still alive — e.g. with multiple power
           sources or because they as the load are not really turned off), because when some devices begin
           battery calibration, they report "OFF" for a few seconds and only then they might report "CAL" after
           switching all the power relays — thus causing false-positives for upsmon FSD trigger.

           A negative value means to disable decreasing the counter of working power supplies in such cases, and
           a zero makes the effect of detected "OFF" state immediate. Built-in default value is 30 (seconds), to
           put an "OFF" state into effect (decrease known-fed supplies count) if it persists for this many
           seconds.

               Note
               so far we support the device reporting an "OFF" state which usually means completely un-powering
               the load; a bug-tracker issue was logged to design similar support for just some manageable
               outlets or outlet groups.

       RBWARNTIME seconds
           When a UPS says that it needs to have its battery replaced, upsmon will generate a NOTIFY_REPLBATT
           event. By default, this happens every 43200 seconds (12 hours).

           If you need another value, set it here.

       RUN_AS_USER username
           upsmon normally runs the bulk of the monitoring duties under another user ID after dropping root
           privileges. On most systems this means it runs as "nobody", since that’s the default from
           compile-time.

           The catch is that "nobody" can’t read your upsmon.conf, since by default it is installed so that only
           root can open it. This means you won’t be able to reload the configuration file, since it will be
           unavailable.

           The solution is to create a new user just for upsmon, then make it run as that user. I suggest
           "nutmon", but you can use anything that isn’t already taken on your system. Just create a regular
           user with no special privileges and an impossible password.

           Then, tell upsmon to run as that user, and make upsmon.conf readable by it. Your reloads will work,
           and your config file will stay secure.

           This file should not be writable by the upsmon user, as it would be possible to exploit a hole,
           change the SHUTDOWNCMD to something malicious, then wait for upsmon to be restarted.

       SHUTDOWNCMD command
           upsmon runs this command when the system needs to be brought down. If it is a secondary, it will do
           that immediately whenever the current overall power value drops below the MINSUPPLIES value above.

           When upsmon is a primary, it will allow any secondaries to log out before starting the local shutdown
           procedure.

           Note that the command needs to be one element in the config file. If your shutdown command includes
           spaces, then put it in quotes to keep it together, i.e.:

               SHUTDOWNCMD "/sbin/shutdown -h +0"

       SHUTDOWNEXIT boolean|number
           After initiating shutdown, should this upsmon daemon itself exit? By doing so NUT secondary systems
           can tell the NUT primary that it can proceed with its own shutdown and eventually tell the UPS to cut
           power for the load. ("Yes" by default)

           Some "secondary" systems with workloads that take considerable time to stop (e.g. virtual machines or
           large databases) can benefit from reporting (by virtue of logging off the data server) that they are
           ready for the "primary" system to begin its own shutdown and eventually to tell the UPS to cut the
           power - not as soon as they have triggered their own shutdown, but at a later point (e.g. when the
           upsmon service is stopped AFTER the heavier workloads).

           Note that the actual ability to complete such shutdown depends on the remaining battery run-time at
           the moment when UPS power state becomes considered critical and the shutdowns begin. You may also
           have to tune HOSTSYNC on the NUT primary to be long enough for those secondaries to stop their
           services. In practice, it may be worthwhile to investigate ways to trigger shutdowns earlier on these
           systems, e.g. by setting up upssched integration, or dummy-ups driver with overrides for stricter
           battery.charge or battery.runtime triggers than used by the rest of your servers.

           This option supports Boolean-style strings (yes/on/true or no/off/false) or numbers to define a delay
           (in seconds) between calling SHUTDOWNCMD and exiting the daemon. Zero means immediate exit (default),
           negative values mean never exiting on its own accord.

       CERTPATH certificate file or database
           When compiled with SSL support, you can enter the certificate path here.

           With NSS:
               Certificates are stored in a dedicated database (data split in 3 files). Specify the path of the
               database directory.

           With OpenSSL:
               Directory containing CA certificates in PEM format, used to verify the server certificate
               presented by the upsd server. The files each contain one CA certificate. The files are looked up
               by the CA subject name hash value, which must hence be available.

       CERTIDENT certificate name database password
           When compiled with SSL support with NSS, you can specify the certificate name to retrieve from
           database to authenticate itself and the password required to access certificate related private key.

       CERTHOST hostname certificate name certverify forcessl
           When compiled with SSL support with NSS, you can specify security directive for each server you can
           contact.

           Each entry maps server name with the expected certificate name and flags indicating if the server
           certificate is verified and if the connection must be secure.

       CERTVERIFY 0 | 1
           When compiled with SSL support, make upsmon verify all connections with certificates.

           Without this, there is no guarantee that the upsd is the right host. Enabling this greatly reduces
           the risk of man-in-the-middle attacks. This effectively forces the use of SSL, so don’t use this
           unless all of your upsd hosts are ready for SSL and have their certificates in order.

           When compiled with NSS support of SSL, can be overridden for host specified with a CERTHOST
           directive.

       FORCESSL 0 | 1
           When compiled with SSL, specify that a secured connection must be used to communicate with upsd.

           If you don’t use CERTVERIFY 1, then this will at least make sure that nobody can sniff your sessions
           without a large effort. Setting this will make upsmon drop connections if the remote upsd doesn’t
           support SSL, so don’t use it unless all of them have it running.

           When compiled with NSS support of SSL, can be overridden for host specified with a CERTHOST
           directive.

       DEBUG_MIN INTEGER
           Optionally specify a minimum debug level for upsmon daemon, e.g. for troubleshooting a deployment,
           without impacting foreground or background running mode directly. Command-line option -D can only
           increase this verbosity level.

               Note
               if the running daemon receives a reload command, presence of the DEBUG_MIN NUMBER value in the
               configuration file can be used to tune debugging verbosity in the running service daemon (it is
               recommended to comment it away or set the minimum to explicit zero when done, to avoid huge
               journals and I/O system abuse). Keep in mind that for this run-time tuning, the DEBUG_MIN value
               present in reloaded configuration files is applied instantly and overrides any previously set
               value, from file or CLI options, regardless of older logging level being higher or lower than the
               newly found number; a missing (or commented away) value however does not change the previously
               active logging verbosity.

SEE ALSO

       upsmon(8), upsd(8), nutupsdrv(8).

   Internet resources:
       The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.1                            01/16/2025                                     UPSMON.CONF(5)