NAME
clone - UPS driver clone
NOTE
This man page only documents the specific features of the clone driver. For information about the core
driver, see nutupsdrv(8).
DESCRIPTION
This driver, which sits on top of another driver socket, allows users to group clients to a particular
outlet of a device and deal with this output as if it was a normal UPS.
EXTRA ARGUMENTS
This driver supports the following settings:
load.off=command
Recommended. Set the command on the "real" UPS driver that will be used to switch off the outlet. You
need both load.off and load.on in order to power cycle the outlet. Otherwise, shutting down the
clients powered by an outlet is a one way street (see IMPORTANT).
load.on=command
Recommended. Set the command on the "real" UPS driver that will be used to switch on the outlet. You
need both load.off and load.on in order to power cycle the outlet. Otherwise, shutting down the
clients powered by an outlet is a one way street (see IMPORTANT).
load.status=value
Recommended. Set the variable on the "real" UPS driver that will be used to indicate the outlet
status (i.e. on/off). If not specified, the clone driver will attempt to keep track of the outlet
status, but this is less reliable.
offdelay=num
Set the timer (in seconds) before the outlet is turned off after the shutdown condition (OB LB) for
this outlet is met or a command to shutdown was issued. Defaults to 120 seconds.
ondelay=num
Set the timer (in seconds) for the outlet to switch on in case the power returns after the outlet has
been switched off. Defaults to 30 seconds.
mincharge=value
Set the remaining battery level when the clone UPS switches to LB (percent).
minruntime=value
Set the remaining battery runtime when the clone UPS switches to LB (seconds).
IMPLEMENTATION
The port specification in the ups.conf(5) reference the driver socket that the "real" UPS driver is
using. For example:
[realups]
driver = usbhid-ups
port = auto
[clone-outlet-1]
driver = clone
port = usbhid-ups-realups
load.on = outlet.1.load.on
load.off = outlet.1.load.off
load.status = outlet.1.status
[...]
IMPORTANT
Unlike a real UPS, you should not configure a upsmon primary mode for this driver. When a upsmon primary
sees the OB LB flags and tells the upsd server it is OK to initiate the shutdown sequence, the server
will latch the FSD status and it will not be possible to restart the systems connected without restarting
the upsd server.
This will be a problem if the power returns after the clone UPS initiated the shutdown sequence on it’s
outlet, but returns before the real UPS begins shutting down. The solution is in the clone driver, that
will insert the FSD flag if needed without the help of a upsmon primary.
CAVEATS
The clone UPS will follow the status on the real UPS driver. You can only make the clone UPS shutdown
earlier than the real UPS driver, not later. If the real UPS driver initiates a shutdown, the clone UPS
driver will immediately follow.
Be aware that the commands to shutdown/restart an outlet on the real UPS drivers are not affected, so if
you tell the real UPS driver to shutdown the outlet of the clone UPS driver, your clients will lose power
without warning.
If you use service management frameworks like systemd or SMF to manage the dependencies between driver
instances and other units, then you may have to set up special dependencies (e.g. with systemd "drop-in"
snippet files) to queue your clone drivers to start after the "real" device drivers.
AUTHOR
Arjen de Korte <adkorte-guest@alioth.debian.org>
SEE ALSO
upscmd(1), upsrw(1), ups.conf(5), nutupsdrv(8)
Dummy driver:
The "repeater" mode of dummy-ups driver is in some ways similar to the clone driver, by relaying
information from a locally or remotely running "real" device driver (and NUT data server).
dummy-ups(8)
Internet Resources:
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/
Network UPS Tools 2.8.1 01/16/2025 CLONE(8)