NAME
upscode2 - Driver for UPScode II compatible UPS equipment
NOTE
This man page only documents the hardware-specific features of the upscode2 driver. For information about
the core driver, see nutupsdrv(8).
SUPPORTED HARDWARE
This driver supports UPS equipment which can be controlled via the UPScode II protocol. This is mainly
Fiskars, Powerware equipment, but also some (probably OEM’ed) products from Compaq.
EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5):
manufacturer=value
Autodetection of this parameter is not possible yet (and it probably never will be). Therefore, this
user-defined string accepts any name. The default is unknown.
input_timeout=value
The timeout waiting for a response from the UPS. Some UPS models have shown to be rather slow,
resulting in frequent messages about empty responses from the UPS. If you see this, try increasing
this value.
output_pace=value
Delay between characters sent to the UPS. This was added for completeness with the above parameter.
It has not shown to be needed yet.
baudrate=value
The default baudrate is 1200, which is the standard for the UPScode II protocol.
full_update_timer=value
Number of seconds between collection of normative values.
use_crlf
Flag to set if commands towards to UPS need to be terminated with CR-LF, and not just CR.
use_pre_lf
Flag to set if commands towards to UPS need to be introduced with an LF. A Compaq T1500h is known to
need this.
COMMANDS
The driver supports the following commands for those UPSes that support them. The available commands are
autodetected during initialization, so you should check availability with upscmd -l.
• test.panel.start - Start UPS self test
• test.battery.start - Start battery self test
• beeper.enable - Enable UPS beeper
• beeper.disable - Disable UPS beeper
• shutdown.return - Shut down in 1 second and wait for power to return
• shutdown.stayoff - Shut down in 1 seconds
• shutdown.reboot - Shut down in 1 seconds and reboot after 1 minute
• shutdown.reboot.graceful - Shut down in 20 seconds and reboot after 1 minute
NOTES
The Powerware UPS models that this driver has been tested against until now have not returned a value for
battery.charge. Therefore, the driver will guesstimate a value based on the nominal battery min/max and
the current battery voltage.
AUTHORS
• Håvard Lygre <hklygre@online.no>
• Niels Baggesen <niels@baggesen.net>
SEE ALSO
The core driver:
nutupsdrv(8)
Internet resources:
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/
Network UPS Tools 2.8.1 03/31/2024 UPSCODE2(8)