Provided by: mbpoll_1.4.11+dfsg-2build1_amd64 bug

Presentation

       mbpoll  is  a  command  line  utility  to  communicate with ModBus slave (RTU or TCP).  It uses libmodbus
       ⟨http://libmodbus.org/⟩.  This is a multiplatform project, the compilation was tested on  GNU  Linux  x86
       and x86_64, Microsoft Windows 7 x86 and GNU Linux ARM 6 (Raspbian).  Although the syntax of these options
       is very close modpoll proconX program, it is a completely independent project.

       mbpoll can:

       -  read  discrete  inputs  - read and write binary outputs (coil) - read input registers - read and write
       output registers (holding register)

       The reading and writing registers may be in decimal, hexadecimal or floating single precision.

Quickstart guide

       The  fastest  and  safest  way  to  install  mbpoll  is  to  use  the  APT  repository  from  piduino.org
       ⟨http://apt.piduino.org⟩, so you should do the following :

           wget -O- http://www.piduino.org/piduino-key.asc | sudo apt-key add -
           sudo add-apt-repository 'deb http://apt.piduino.org stretch piduino'
           sudo apt update
           sudo apt install mbpoll

       This  repository  provides mbpoll and libmodbus (version 3.1.4) packages for i386, amd64, armhf and arm64
       architectures.  In the above commands, the repository is a Debian Stretch distribution, but you can  also
       choose  Ubuntu  Xenial  by  replacing  stretch with xenial.  It may be necessary to install the software-
       properties-common package for add-apt-repository.

       For Raspbian you have to do a little different :

           wget -O- http://www.piduino.org/piduino-key.asc | sudo apt-key add -
           echo      'deb      http://raspbian.piduino.org      stretch      piduino'      |      sudo       tee
       /etc/apt/sources.list.d/piduino.list
           sudo apt update
           sudo apt install mbpoll

       The Raspbian repository provides Piduino packages for armhf architecture for Stretch only.

Build from source

       For example, for a debian system:

       * Install libmodbus ⟨https://github.com/stephane/libmodbus.git⟩ (Version >= 3.1.4) :

               $ sudo apt-get install build-essential libtool git-core autoconf
               $ git clone https://github.com/stephane/libmodbus.git
               $ cd libmodbus
               $ ./autogen.sh
               $ ./configure
               $ make
               $ sudo make install

       You  can  also  install  it  with apt if the version of libmodbus is greater than or equal to 3.1.4.  For
       example to query a debian system:

           $ apt-cache show libmodbus-dev

       * Install piduino ⟨https://github.com/epsilonrt/piduino/tree/dev⟩ only if you want to  manage  the  RS485
       with a GPIO signal:

               $ sudo apt-get install cmake libcppdb-dev pkg-config libsqlite3-dev sqlite3
               $ git clone https://github.com/epsilonrt/piduino.git
               $ cd piduino
               $ git checkout dev
               $ mkdir build
               $ cd build
               $ cmake ..
               $ make
               $ sudo make install

       * Generate Makefile with cmake:

               $ sudo apt-get install cmake pkg-config
               $ cd mbpoll
               $ mkdir build
               $ cd build
               $ cmake ..

       * Compile and install mbpoll:

               $ make
               $ sudo make install
               $ sudo ldconfig

       If you prefer, you can in the place of direct compilation create a package and install it:

               $ make package
               $ sudo dpkg -i * .deb

       That's all !

Examples

       The  following  command  is used to read the input registers 1 and 2 of the slave at address 33 connected
       through RTU /dev/ttyUSB2 (38400 Bd)

       ---

               $ mbpoll -a 33 -b 38400 -t 3 -r 1 -c 2 /dev/ttyUSB2

               mbpoll 0.1-10 - FieldTalk(tm) Modbus(R) Master Simulator
               Copyright (c) 2015 epsilonRT, All rights reserved.
               This software is governed by the CeCILL license ⟨http://www.cecill.info⟩

               Protocol configuration: Modbus RTU
               Slave configuration...: address = [33]
                                       start reference = 1, count = 2
               Communication.........: /dev/ttyUSB2, 38400-8E1
                                       t/o 1.00 s, poll rate 1000 ms
               Data type.............: 16-bit register, input register table

               -- Polling slave 33... Ctrl-C to stop)
               [1]:      9997
               [2]:      10034
               -- Polling slave 33... Ctrl-C to stop)
               [1]:      10007
               [2]:      10034
               -- Polling slave 33... Ctrl-C to stop)
               [1]:      10007
               [2]:      10034
               -- Polling slave 33... Ctrl-C to stop)
               [1]:      10007
               [2]:      10034
               ^C--- /dev/ttyUSB2 poll statistics ---
               4 frames transmitted, 4 received, 0 errors, 0.0% frame loss

               everything was closed.
               Have a nice day !

Help

       A complete help is available with the -h option:

           usage : mbpoll [ options ] device|host [ writevalues... ] [ options ]

           ModBus Master Simulator. It allows to read and write in ModBus slave registers
                                    connected by serial (RTU only) or TCP.

           Arguments :
             device        Serial port when using ModBus RTU protocol
                             COM1, COM2 ...              on Windows
                             /dev/ttyS0, /dev/ttyS1 ...  on Linux
                             /dev/ser1, /dev/ser2 ...    on QNX
             host          Host name or dotted IP address when using ModBus/TCP protocol
             writevalues   List of values to be written.
                           If none specified (default) mbpoll reads data.
                           If negative numbers are provided, it will precede the list of
                           data to be written by two dashes ('--'). for example :
                           mbpoll -t4:int /dev/ttyUSB0 -- 123 -1568 8974 -12
           General options :
             -m #          mode (rtu or tcp, TCP is default)
             -a #          Slave address (1-255 for rtu, 0-255 for tcp, 1 is default)
                           for reading, it is possible to give an address list
                           separated by commas or colons, for example :
                           -a 32,33,34,36:40 read [32,33,34,36,37,38,39,40]
             -r #          Start reference (1 is default)
             -c #          Number of values to read (1-125, 1 is default)
             -u            Read the description of the type, the current status, and other
                           information specific to a remote device (RTU only)
             -t 0          Discrete output (coil) data type (binary 0 or 1)
             -t 1          Discrete input data type (binary 0 or 1)
             -t 3          16-bit input register data type
             -t 3:hex      16-bit input register data type with hex display
             -t 3:int      32-bit integer data type in input register table
             -t 3:float    32-bit float data type in input register table
             -t 4          16-bit output (holding) register data type (default)
             -t 4:hex      16-bit output (holding) register data type with hex display
             -t 4:int      32-bit integer data type in output (holding) register table
             -t 4:float    32-bit float data type in output (holding) register table
             -0            First reference is 0 (PDU addressing) instead 1
             -B            Big endian word order for 32-bit integer and float
             -1            Poll only once only, otherwise every poll rate interval
             -l #          Poll rate in ms, ( > 10, 1000 is default)
             -o #          Time-out in seconds (0.01 - 10.00, 1.00 s is default)
           Options for ModBus / TCP :
             -p #          TCP port number (502 is default)
           Options for ModBus RTU :
             -b #          Baudrate (1200-921600, 19200 is default)
             -d #          Databits (7 or 8, 8 for RTU)
             -s #          Stopbits (1 or 2, 1 is default)
             -P #          Parity (none, even, odd, even is default)
             -R [#]        RS-485 mode (/RTS on (0) after sending)
                            Optional parameter for the GPIO RTS pin number
             -F [#]        RS-485 mode (/RTS on (0) when sending)
                            Optional parameter for the GPIO RTS pin number

             -h            Print this help summary page
             -V            Print version and exit
             -v            Verbose mode.  Causes mbpoll to print debugging messages about
                           its progress.  This is helpful in debugging connection...

       --- > Copyright © 2015-2019 Pascal JEAN, All rights reserved.

       > mbpoll is free software: you can redistribute it and/or modify it under the terms of  the  GNU  General
       Public License as published by the Free Software Foundation, either version 3 of the License, or (at your
       option) any later version.

       >  mbpoll  is  distributed in the hope that it will be useful, but WITHOUT ANY WARRANTY; without even the
       implied warranty of MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.   See  the  GNU  General  Public
       License for more details.

       >  You  should  have  received  a  copy  of the GNU General Public License along with mbpoll. If not, see
       ⟨http://www.gnu.org/licenses/⟩.

                                                                                                        mbpoll()